Analysis of a remote building energy auditing system using internet

Citation
International journal on architectural science, v.2, no.4, 2001, pp. 129-134
Abstract
In order to facilitate on-line energy auditing of building energy consumption, a remote control system using internet has been installed. This control system enables diagnostics on the HVAC system so that energy conservation measures can be performed with successful result. Measured data indicated that the chiller plant runs at 0.71 kW/RT or about 18% higher power consumption than average units. Further on-line measurement receives that the chiller always runs with Inlet guided vane partially opened, results in unfavorable loading conditions. (1) Introduction (2) System simulation (3) Designing new remote energy auditing system with internet (4) System diagnostics and experimental investigation (5) Conclusions (6) Abbreviation (7) References
Description
Notes: Heating, Ventilation, Air conditioning